Chapter 7 or note special.
Attic fau framing detail.
If the attic and roof framing is a prefabricated engineered truss system an engineering report wet stamped and signed by a licensed engineer shall be submitted for review and approval prior to issuance of a building permit.
If the attic and roof framing is a prefabricated engineered truss system an engineering report wet stamped and signed by a licensed engineer shall be submitted for review and approval prior to issuance of a building permit.
Cmc chapter 9 attic furnace diagram.
If the attic and roof framing is a pre fabricated engineered truss system an engineering report wet stamped and signed by a licensed engineer shall be submitted for review and approval prior to issuance of a building permit.
Fau unit shall be doubled with a minimum 2x6 joists.
Install passageway platform minimum 24 inches width and maximum 20 feet in length to fau.
An attic in which a fau is installed shall be accessible by an opening and passageway 30 x 30 in size.
If the attic and roof framing is a pre fabricated engineered truss system an engineering report wet stamped and signed by a licensed engineer shall be submitted for review and approval prior to issuance of a building permit.
Attic furnace passageway minimum dimensions requirements.
30 inches high 762 mm 22 inches wide 559 mm 20 feet max length 6096 mm measured along the center line between the attic access opening and the attic furnace.